Smoke Vent EA-K-30 Chain Actuator - 24V, 300N

by easivent
£163.00

Chain actuator available exclusively from Easivent. Tested to EN 12101, available in five stroke lengths.

This 24V, 300N chain actuator has programmable options include adjusting the length of stroke via SimonLink software (upon request prior to dispatch).


Suitable for Smoke ControlSuitable for Natural Ventilation

Certified to EN-12101 the EA-K-30 is a state of the art chain actuator with low noise operation making it ideal for both smoke & natural ventilation systems. Utilizing proven technology from the best selling Folding Arms these chain drives combine power with elegance. The whole range can be used for tandem installations without the need for additional software or equipment.

 

Special Features Include: 

·         Integrated tandem function for windows requiring one or more actuators
·         Interconnecting link through for tandem applications
·         Programmable upon request prior to dispatch
·         Soft start
·         Soft Close for the last 75 mm
·         Feedback - Choice of voltage or dry contact

 

Chain actuator stroke length: 

 Ref - 400mm: M25315

Ref - 600mm: M25316

Ref - 800mm: M25317

Ref - 1000mm*: M25318

Ref - 1200mm*: M25319

 

Nominal voltage: 24 V DC +/- 15%
Nominal current: 1.4 A
Force: 300 N
Cut-off: Integrated, electronic power cut-off
Programmable: Via SimonLink Software (upon request prior to dispatch)
Full Load Speed: 11 mm/s
Ingress protection: IP 32
Switch on duration: ED 30 %
Temperature range: 0 °C to + 75 °C
Connection cable: Silicone 3 (6) x 0.75 mm² (Length 3.000 mm)
Housing: Aluminium EV1 anodized
Weight: 2.00 kg
Dimensions: 467(-764)mm L x 37mm D x 35mm H (please allow 40mm for cabling)

Power supply used must remove the 24V supply for a minimum of 500ms prior to the reverse polarity supply being applied. If the control panel you are using does not provide this we do provide a dedicated timer that can be used.

 

For further details, please view our datasheet 

*Please note this actuator stroke length will not fully open within the required 60 seconds for smoke control purposes

Don't forget your brackets...

Outward Opening Actuator Bracket 

Inward Opening Actuator Bracket & Wing Bracket also required for Inward Opening

You recently viewed

Clear recently viewed